A near-perfect repair, missing one part
Not every chimney problem comes from an old, neglected fireplace. Sometimes it comes from a repair that was almost right but not quite. This featured project, for longtime Priddy Chimney customers in Bethesda, Maryland, is a great example of how skipping one small, code-required component can cause big, persistent problems, including an ominous gas smell inside the home.
Overburning Gas Logs and a Lingering Gas Smell
The homeowners, returning clients Priddy Chimney had worked with at a previous house years earlier, had two gas log fireplaces in their new Bethesda home: one in an upstairs family room, and one in the basement, both venting into the same multi-flue chimney.
The upstairs set used ceramic “cannonball” logs, and the burner had been positioned too far forward in the firebox. As a result, the flames were scorching the front lintel of the firebox and over-burning the ceramic balls themselves, well beyond normal wear. The homeowners were also periodically smelling gas inside the house, which is never a symptom to ignore.

Ceramic cannonball logs overburning
The Root Cause: A Missing Throat Damper
The issue became quickly apparent. The chimney flue had been relined by another company prior to this call but whoever performed that reline installed only a top-of-flue damper, the kind that opens and closes with a chain pull at the very top of the chimney. That’s a completely normal, correct component for a wood-burning fireplace.
However, here’s the issue: you cannot rely on a top-mounted damper alone with gas logs. If a top damper is fully closed, it traps gas from the pilot light inside the flue and, potentially, inside the home. That’s where the persistent gas smell this family was experiencing was coming from.
Montgomery County code requires a cast iron throat damper, installed directly in the throat, just above the firebox opening, on any fireplace running gas logs. That throat damper must be fitted with a safety clip that physically prevents it from ever being pulled fully shut. Even if a homeowner tries to close it, the clip stops the damper about 1.5 inches short, leaving a permanent gap so pilot gas can always vent safely.
Why Gas Logs Overburn in the First Place
This project also creates a good opportunity to explain why gas log sets overburn in cold weather, a complaint we hear constantly, especially heading into the fall and winter months.
Draft in a chimney is created by heat: warm air rises and pulls outside air up and out through the flue. A gas log pilot light, on its own, doesn’t generate much heat, nowhere near enough to establish a strong draft on a cold day. So when a gas log set is first turned on, it has to push a column of cold air sitting in the flue all the way up and out before the flue really starts drawing properly.
Until that happens, you get a downdraft competing with the intended draft, cold air pushing down while warm exhaust tries to push up. The result is what’s called “back-puffing” or backdrafting, and it shows up as flames overburning logs, scorching ceramic balls, or licking the firebox, because the flame and heat aren’t being pulled up and away the way they should.
In this home’s case, the problem was made worse by two compounding issues at once: a missing throat damper, and a burner set too far forward, meaning it wasn’t even positioned directly under the flue opening where the draft is strongest. This needed to be remedied quickly to prevent further damage.
Priddy Chimney's Fix: A Full Reset Top to Bottom
For both fireplaces, Priddy Chimney’s crew performed a complete gas log service and correction. To do this, we:
-Removed the gas log sets from both fireboxes
-Repaired the smoke chambers above each firebox
-Repainted both fireboxes in high-temperature black finish
-Installed proper cast iron throat dampers, correctly fitted with safety clips, in both the piano room fireplace and the basement fireplace
-Repositioned each burner roughly 5 inches back in the firebox so it sits directly beneath the flue opening where the cast iron damper is instead of forward toward the firebox opening
-Cleaned and reinstalled the log sets, with a full burner cleaning and maintenance service ahead of the fall heating season
An added bonus of the cast iron throat damper beyond meeting code: unlike a wide-open throat, a cast iron damper actually heats up during use and radiates some of that warmth back into the room, rather than letting all of it escape straight up the flue.
How The Safety Clip is Installed Matters
One detail that’s easy to overlook but makes or breaks the entire repair: where the safety clip is attached on the damper.
The correct installation places the safety clip on the damper’s operating handle. Positioned there, the clip physically stops the handle from being pulled far enough to close the damper past its safe minimum opening.
The incorrect installation places the clip on the damper flap itself. In that position, the clip only rests against the flap and allows it to lean open roughly half an inch, which can shift, get bumped, or fail to reliably hold that gap over time.
If a technician tells you your gas fireplace has a safety clip, it’s worth asking specifically where it’s installed. A clip on the flap can look correct at a glance but doesn’t actually guarantee the damper can’t be closed too far, which is the point of the code requirement in the first place.


(Left): Correct Installation (Right): Incorrect Installation
What Bethesda and Montgomery County Homeowners Need to Know
If you have gas logs in Montgomery County, Maryland, or you’re noticing similar issues in your own fireplace, a few takeaways from this project are worth keeping in mind:
A chimney reline alone doesn’t guarantee your gas logs are code-compliant. A top-mounted, chain-pull damper is correct for wood but not sufficient on its own for gas logs.
Gas logs require a cast iron throat damper with a properly placed safety clip on the handle, not the flap.
Any lingering gas smell should be taken seriously and inspected promptly; it’s often a sign of a venting or damper issue, not the gas logs themselves malfunctioning.
Overburning logs or scorched ceramic balls are not just cosmetic wear. It usually points to a burner positioning issue, a draft problem, or both.
If you have two fireplaces sharing one multi-flue chimney, it’s common for both to develop the same issue at the same time, since they were likely installed or serviced together originally.
A gas log set that’s properly positioned, cleaned, and paired with a correctly installed throat damper should run cleanly all season, without the smell, the scorching, or the guesswork.
Noticing gas odor, overburning logs, or a fireplace that just doesn’t seem to draft right in your Bethesda or Montgomery County home? Priddy Chimney Solutions can inspect your damper setup and get your gas logs running safely before the weather turns. Contact us to schedule a visit.